0.6-1 kV-CV

0.6/1KV-CV

0.6/1 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED PVC SHEATHED FLAM RETARDANT POWER CABLE

 Conductor

Concentric Stranded and compacted round
annealed copper

Single-core :  Size 1.5 mm² up to 1,000 mm²

Multi-cores :  Size 1.5 mm² up to 400 mm²

 Insulation Cross-linked Polyethylene (XLPE)
 Core Identification

Single-core : Natural (translucent)
2 Cores : Blue and Brown
3 Cores : Brown, Black and Grey
4 Cores : Blue, Brown, Black and Grey
Other colors are available on customer request

 Sheath Black polyvinyl chloride (PVC/ST2)
Classification

: Maximum conductor temperature 90 °C
: Circuit voltage not exceeding 1,100 Volts
Rated voltage (Uₒ/U) 0.6/1 kV
     600 Volts between Line-to-Earth
     1,000 Volts between Line-to-Line

Testing voltage 3,500 Volts
Reference standard IEC 60502-1, IEC 60228, IEC 60332-1

Use for installation in open tray, conduit, underground
duct trench or direct burial in ground, at wet or dry location.

Group 3211
Group 3211
Group 3211